Laars EBP175 Endurance Hydronic Boiler w. Domestic Hot Water
Item Number: 11721
Manufacturer Name: Laars Heating Systems Company
Manufacturer Part No: EBP175
|
|
Specifications:
- Input (MBTU/h): 102.9-175.3
- Input (kW): 30.1-51.4
- Output (MBTU/h): 88.6-151.0
- Output (kW): 25.4-44.2
- AFUE%: 86.1
- Continuous GPH @ 100°F Rise: 183
- Minimum Clearances from Combustible Materials:
- Back & Front: 1"
- Sides: 1"
- Top (Alcove Install): 1"
- Top (Closet Install): 22"
- Vent: Concentric, Direct: 0"
- Vent: Category IV: 3"
Features:
- Design certified and tested to ANSI standard Z21.13
- Designed and constructed in accordance with the ASME Boiler & Pressure Vessel Code, Sections II, IV, and IX
- Maximum working pressure - water 30 psi, ASME rated
- Hydrostatic test pressure at factory - 60 psi
- Minimum gas supply pressure - 4" w.c.
- Maximum gas supply pressure - 13" w.c.
- 85+% AFUE
- Sealed stainless steel combustion chamber
- Hot surface ignition
- Automatic burner modulation from 57% to full fire
- NOx levels less than 25 ppm
- Venting - Direct vent (sealed combustion with ducted combustion air in concentric vent) or Category III
- Design certified for installation directly on a combustible floor (except carpeting)
- One-inch clearance on all 4 sides
- Zero clearance from combustibles to the vent when concentric venting is used
- Electrical: 115V-60HZ-1PH less than 15 Amps with 24V transformer mounted and wired
- Outdoor reset with the addition of outdoor air sensor (limited temperature range available for EBP models)
- Control overrides outdoor reset when air sensor is faulty
- Easy-to-use viewing and programming menus
- 3-Character alphanumeric display of temperatures and fault codes
- Displays fault codes for supply sensor, return sensor, tank sensor (EBP only), outdoor air sensor, internal control, and lockout
- Displays 6 temperatures: supply water, return water, tank water (EBP only), heat exchanger temperature rise, outdoor air temperature (when outdoor reset is used), and calculated set point (when outdoor reset is used)
- Control LEDs indicate pump energized, gas valve energized and attempt to ignite
- Ignition control LEDs show faults for erroneous flame signal, internal error and lockout
- Low water temperature feature - attempts to run the pump when supply water temperature falls below 39ðF
- Built-in circulating pump and by-pass loop
- Equipped with anti-condensing controls
- Pump exerciser to ensure pump remains free from corrosion
- Built-in safety limit
- Copper finned, cylindrical tube design heat exchanger brazed into ASME bronze headers
- EBP united store 20 gallons of boiler water to provide instantaneous domestic hot water production through a brazed plate heat exchanger, with DHW priority
-
20 Year limited warranty
For more information on this product please view the Sheet(s) below: Laars Endurance EBP, EDP, EDN Installation Manual Laars Endurance Parts List Laars Endurance Questions And Answers Booklet
|
Laars 2400-452 3"/5" Concentric Terminal w/ Screen - Replaces 2400-406
|
Laars 2400-422 3"/5" Concentric Vertical Termination Adapter
|
Laars 2400-364 Vent Exhaust Pipe, 3" x 4' (SS AL 29-4C)
|
Laars 2400-362 Fresh Air Tee
|
Laars 2400-443 Wiring Harness
|
Laars 2400-421 3"/5" Concentric Condensate Trap
|
Laars 2400-423 3"/5" x 12" Concentric Pipe
|
Laars 2400-539 Anti-Condensing Valve, Operator Only
|
Laars 2400-370 Vertical Vent Cap
|
Laars 2400-420 3"/5" Telescoping Concentric Boiler Adapter
|
Laars 2400-433 3"/5" x 24" Concentric Pipe
|
Laars 2400-424 3"/5" x 12.5 - 19.5" Telescoping Concentric Pipe
|
Laars 2400-435 5" x 4" Fresh Air Tee & Boiler Adapter
|
Laars 2400-418 3"/5" 90 Elbow
|
|
Laars 2400-548 Gas Valve, Honeywell
|
Laars 30-310 Wiring Harness Assembly
|
Laars 2400-518 Burner w/ Gaskets
|
Laars R2028200 Water Flow Switch (Replaces 2400-542) Individual flow switch # E2337400
|
Laars 2400-425 3"/5" x 36" Concentric Pipe
|
Laars 2400-538 Valve, Anti-Condensing
|
Laars 2400-546 Boiler Control For Older Style Models (Blue Color)
|
Laars 2400-570 Heat Exchanger, DHW
|
Laars 2400-428 Vent Terminal Extension
|
Laars 2400-441 Ignition Control
|
Price: Currently out of stock
Laars 2400-439 Boiler Control
|
Laars 2400-524 Blower, Combustion Air, w/ Gaskets - Laars recommends to change 2400-442 when replacing 2400-524
|
Laars 2400-148 Field Service Kit
|
Laars 2400-386 Pump, UP26-99F, Grundfos
|
Price: Discontinued by Manufacturer
Laars 2400-520 Transfer Tank
|
Product Reviews
|
|
|