Honeywell S9200U1000 Universal Hot Surface Ignition Integrated Furnace Control

<< Previous in Honeywell Transformers / Relays Next in Honeywell Transformers / Relays >>
Price: $151.30
Item Number: S9200U1000
Manufacturer Name: Honeywell
Manufacturer Part No: S9200U1000

Overview

Universal Integrated Furnace Control offers universal compatibility and diagnostics. It replaces a large number of furnace control models in single-stage warm air furnaces. Uses 120Vac hot surface igniter. Includes instructions and special wire harnesses for easy replacement.

Features

  • • Cross reference and wire harnesses provided for simple replacement over 195 existing furnace controls.
  • Main burner ignition using a 120V hot surface igniter.
  • Flame rectification circuit to monitor flame presence.
  • Monitoring of system pressure switch, high temperature limit, and rollout functions.
  • Appliance operation/safety requirements controlled via microprocessor.
  • Controls circulating fan motor based on appliance requirements, in response to a conventional low voltage thermostat.
  • LED system status, performance and diagnostic indication.
  • Twinning capability

Product Specifications

  • Application: Single stage warm air furnaces
  • Frequency: 60 Hz
  • Operating Humidity Range (% RH): 0% to 95% non-condensing
  • Operating Temperature Range (F): -40 F to +175 F
  • Operating Temperature Range (C): -40 C to +79 C
  • Flame Failure Response Time (sec): 2 Seconds max @ 1µA
  • PrePurge: 30 seconds
  • PostPurge: 15 seconds
  • Cool Fan On Delay: 5 seconds
  • Cool Fan Off Delay: 0 or 60 seconds
  • Line Voltage: 120 Vac (97-132 Vac)
  • Low Voltage: 24V (18-30 Vac)
  • Igniter Current: 5 A resistive @ 120VAC
  • Thermostat Anticipator Setting: (Stage 1 only) 100mA
  • HSI Warmup Time: 17/27 or 30/30 seconds
  • Trial For Ignition: 4, 6, or 8 seconds
  • Interpurge: 60 seconds
  • Ignition Trials: Three, two tries if flame is not sensed
  • Number of LEDs: 3
  • Heat On Fan Delay: 30 or 60 seconds
  • Heat Off Fan Delay: 60, 90, 120, or 180 Seconds
  • Gas Control Used With: Any 24Vac redundant, direct ignition gas control rated at 1.5A or less. Honeywell VR8205 recommended.
  • Cooling Contactor Used With: Any 24Vac contactor rated at 1.0A or less
  • Induced Draft Blower Load: 2.2FLA / 25LRA max @120Vac
  • Ciculator Load: 14.5FLA / 25LRA max @120Vac
  • Type of Fan Used With: Standard Induction-Type Circulating Fan