Browse Categories

Honeywell D146M1040 Differential Pressure Regulator

<< Previous in Honeywell Replacement Parts Next in Honeywell Replacement Parts >>
Price: $293.24
Item Number: D146M1040
Manufacturer Name: Honeywell
Manufacturer Part No: D146M1040

Overview

The differential pressure regulator eliminates excessive pump head pressure, when most radiator valves are closed due to reduced demand, by controling flow through a bypass line when the difference between supply/return exceeds the setpoint.

Features

  • Install between supply and return sides of a hydronic system to stabilize pressure differential and reduce the effects of demand changes.
  • Control maintains a constant differential between the two sides by opening a bypass whenever the difference between supply and return reaches the setpoint.
  • Provides silent, trouble-free service.
  • Easy installation; requires no electrical hookup.
  • Easy adjustment of pressure by turning regulating cap.
  • Built-in differential pressure indicator.
  • Brass valve body with thermoplastic and stainless steel parts.
  • Diaphragm of EPDM.

Product Specifications

  • Dimensions (in.): 8 1/2 in. high x 4 1/4 in. wide
  • Dimensions (mm): 213 mm high x 109 mm wide
  • Includes: Built-in differential pressure indicator
  • Operating Temperature Range (F): 230 F Maximum
  • Operating Temperature Range (C): 110 C Maximum
  • Connection Type: Angle type, female threaded NPT
  • Pipe Size (inch): 1 1/4 in.
  • Pipe Size (DN): DN32
  • Capacity: 395,000 Btu/hr; 50 gpm
  • Valve Type: Pressure Regulating Valve
  • Materials (Body): Brass (body), Stainless steel and engineered thermoplastics. EPDM diaphragm.
  • Outlet Pressure Adjustment Range (psi): 0-17 psi
  • Max. Inlet Pressure Rating (psi): 85 Psi

Product Reviews

Rate This Product:
or Create a Review
(0 Ratings, 0 Reviews)
Shopping Cart