|
Honeywell VR8345Q4563 Intermittent / Direct Ignition Gas Valve
Item Number: VR8345Q4563
Manufacturer Name: Honeywell
Manufacturer Part No: VR8345Q4563/U
* Whole number only
|
|
VR8345Q4563/U Universal 24 Vac, Standard Opening, Two-Stage, Intermittent / Direct Ignition Gas Valve 3/4 x 3/4"
Overview
Universal electronic ignition combination gas control for use with direct spark ignition, hot surface ignition or intermittent pilot ignition in 24 Vac, gas-fired appliances, with capacities from 20 to 200 cfh (VR8245M) or 30 to 415 cfh (VR8345M).
Features
- Control includes manual valve, two automatic operators, pressure regulator, pilot adjustment, pilot plug and ignition adapter.
- Replaces many IP, HSI, or DSI gas control.
- For use with natural or manufactured gas or LP gas.
- Includes converter kit to adapt from natural to LP gas.
- Compact size.
- All adjustments and wiring connections accessible from top of control.
- Four-inch swing radius allows easy rotation into position inside the tightest furnace vestibules.
- Clearly marked, keyed terminal block allows quick attachment of wires and IP/DSI/HSI jumper.
- Internal inlet screen blocks contaminants in gas line from entering valve.
Product Specifications
- Application: Two Stage
- Dimensions (in.): 5 3/8 in. high x 4 1/16 in. wide x 2 11/16 in. deep
- Dimensions (mm): 135 mm high x 104 mm wide x 69 mm deep
- Includes: Two 3/4 x 1/2 in. reducer bushings; Natural to LP Conversion Kit
- Item Type: Product
- Mounting: 0 to 90 degrees in any direction from the upright position of the gas control knob, including vertically.
- Frequency: 50 Hz; 60 Hz
- Approvals, CSA: CSA International: 112395
- Tradeline Value: Universal
- Electrical Connections: 1/4 in. quick-connect male terminals
- Voltage: 24 Vac
- Operating Temperature Range (F): -40 F to +175 F
- Operating Temperature Range (C): -40 C to +79 C
- Body Pattern: Straight-through
- Opening Characteristics: Standard Opening
- Pressure Ratings (psi): 1/2 psi
- Pressure Ratings (kPa): 3.5 kPa
- Inlet/Outlet Size (in.): 3/4 in. x 3/4 in.
- Pilot Gas Outlet: Compression fitting for 1/4 in. OD tubing
- Pressure Tapping: 1/8 in. NPT with plug
- Type of Fuel: Natural (LP with included conversion kit)
- Capacity (kBtuh): At 1 in. wc p.d.-- 300,000 BTUh: 30,000 BTUh minimum: 415,000 BTUh maximum Natural Gas
- Pressure Regulator: Standard
- Pressure Regulator Setpoint (in. wc): 1.7 in. wc low; 3.5 in. wc high
- Pressure Regulator Setpoint (kPa): 0.48 kPa low; 0.87 kPa high
- Ignition Type: Direct Ignition; Intermittent Pilot
|
Product Reviews
|
|
|